Series 2000
Power output | Standby power | Continuous / Prime / Peak power | ||||
Standardized backup (3D) | Standardized | Data center | Prime (3B) | Peak (3G) | ||
backup with overload (3E) | continuous (3F) | |||||
50 Hz / 1500 rpm | kVA | kVA | kVA | kVA | kVA | |
Series 2000 | 12V2000 DS1000 | 1010 | 800 | – | 800 | – |
16V2000 DS1100 | – | 1000 | 1000 | 1000 | 1000 | |
16V2000 DS1250 | 1250 | 1135 | – | 1135 | – | |
18V2000 DS1400 | 1400 | 1250 | 1250 | 1250 | 1250 |
Load | Variable | Variable | Continuous | Variable | Continuous |
Load factor | ≤ 85% | ≤ 85% | ≤ 100% | ≤ 75% | ≤ 100% |
10% overload (ICXN) | no | yes | yes | yes | yes |
Max. operating hours (per year) | 500h | 500h | Unlimited* | Unlimited | 1,000h, 500h with 100% load w/o interruption |
Uptime compliant | Tier I & Tier II | Tier I & Tier II | Tier III & Tier IV | Tier I & Tier II | Tier I & Tier II |